Fire hazard is a very sensitive and important control point; In the past, many fire accidents were caused by poor waste gas treatment equipment control, how to control the hidden danger of waste gas treatment equipment fire is the key point of the design. Fire damper frame machine is one of the effective measures to control the fire effectively.
Precautions When Using Fire Damper Frame Machine
The fire damper automatically closes when the explosion-proof dust removal equipment runs abnormally to prevent a fire in one place from affecting other floors.
- Selection of fire damper temperature: Fire dampers have a variety of temperatures to choose from according to the usage scenario: 70 degrees to 150 degrees, etc.; commonly used waste gas, generally set a fire damper of 70 degrees; high-temperature waste gas, choose 150 degrees or more fire protection valve.
- Selection of fire damper material: Galvanized fire dampers can be used for non-corrosive gases; if the gas is severely corrosive, fireproof materials need to be considered; and for strong acid waste gas, 316L stainless steel fire dampers need to be used.
- There are requirements for installing fire dampers: usually, the distance between the fire dampers and the wall is no more than 30 cm, and the pipes in the wall also need to be resistant to high temperatures.
- Fire dampers can usually be linked with fans or fire sprinklers so that when a fire occurs, the fire dampers can be closed, and the fans can be turned off to stathe rt fire sprinklers at the same time.
- The fire damper of explosion-proof dust removal equipment can effectively prevent the spread of fire. Proper installation and selection of the fire damper frame machine will effectively play the role of the fire damper.
Fire Damper Operation Principle And Smoke And Fire Resistance
fire damper frame machine is necessary safety equipment in the supply and returns air pipelines of ventilation and air conditioning systems. The function of system linkage control, how to correctly install the fire damper to promote environmental safety, and what is its operating principle?
Orientation Of Fire Damper
- Fire dampers can generally be installed on the main air duct of the air outlet of air conditioning equipment such as fresh air units and air conditioning units.
- It can be installed when the air duct passes through the fire compartment.
- It is installed when the air duct passes through the elastic settlement joint of the building structure.
- When the air duct passes through a flammable workshop or room, it cannot be prevented.
Principle Of The Operating Device Of Fire Damper
The top of the fuse core rod is usually stuck on the fork plate on the valve shaft (blade shaft) so that the valve is in a normally open state. When a fire occurs, the airflow temperature in the pipeline rises to the point where the fuse is easy to fuse and fuse the fusible piece. The tension spring pushes the core rod, disengages the fork plate, and the valve shaft is rotated to close the valve by the effect of the torsion spring.
It is installed in the air duct system of the central air conditioner. The working principle is the temperature control of the extremely fusible alloy. The valve is closed by the effect of gravity and the spring structure. When a fire breaks out, the flame invades the air duct, and the high temperature makes the fusible alloy on the valve. Melting or deforming the memory alloy, the valve is automatically closed, and it is used in the place where the air duct and the fire compartment run through.
If the normal air volume needs to be adjusted, the valve opening can be adjusted through the handle linked with the valve shaft (blade shaft), and the butterfly valve will fix its position when it reaches the request. There are ring teeth at the contact between the handle and the fork plate to prevent sliding and meshing, and the valve opening will remain unchanged after being adjusted.
An Important Effect Of Smoke And Fire Dampers
Fire dampers are important components in ventilation, air harmony, and smoke prevention, and exhaust systems. What important effects do they play in the system?
A fire damper is a valve used to block the passage of smoke and flame from the fire area and can meet the requirements of fire resistance stability and fire integrity within a certain period.
To reduce the losses caused by fire to the minimum level, it is necessary to take effective fire prevention and smoke prevention measures to control the extension of the fire, and the appropriate setting of fire dampers in the ventilation, air conditioning, and smoke prevention and exhaust systems plays an important role in effect.
In the air duct of the air conditioning system, the purpose of the fire damper is to quickly block the airflow in the event of a fire to prevent the fire from extending. When a fire occurs, the air duct is affected by the surrounding temperature, and the temperature rises.
At a certain temperature, the fusible sheet is blown. The valve plate originally connected by the fusible sheet is immediately separated from the fusible sheet and closed to prevent the passage of air. To continuously supply air to the system, fire damper frame machine electrical signals, and interlocking devices, the valve plate can issue a signal when it is closed to make the fan run intermittently.
The fire damper frame machine also has the effect of preventing smoke and fire. In the air supply system, the air sent by the blower must be distributed to the branch pipes through the main pipe; in the smoke exhaust system, the flue gas enters the exhaust pipe from the branch pipe to the main pipe. The exhaust fan is exhausted.
When a fire breaks out in a building, in the ventilation and air conditioning system, to prevent the fire from extending through the air supply system, when the gas temperature in the air supply system reaches 70 °C, the fuse on the fire damper will act, and the valve will also quickly close the valve. Block the passage of smoke and fire along the air duct.
Similarly, when a fire breaks out in the smoke exhaust system, the smoke exhaust valve is opened to stop the exhaust. When the temperature is 280°C, the smoke and fire dampers and the fuses on the smoke vents act, and the valves must be actively closed to prevent the smoke from being discharged.
It can be seen that the fire dampers and smoke exhaust valves have achieved the general rule of opening, and the off-break, the smoke, and fire blocking. Effect.